California Title 24 takeoff: connect insulation, glazing and lighting controls

For California nonresidential bids, reconcile insulation assemblies, rough-opening glazing areas and daylight control zones against the 2025 Energy Code.

Guide11 min read

Published

Construction scaffolding interior

Bring a current or completed project and see how Piper saves review time, surfaces scope gaps, and applies your company's knowledge.

Book a demo
On this page
  1. Establish the applicable path before measuring the package
  2. Read the compliance sheets as a cross-trade register
  3. Insulation quantities belong to assemblies and layers
  4. Illustrative example: one wall area, two priced insulation lines
  5. Glazing needs two area bases and an orientation check
  6. Illustrative example: the total passes while the west elevation does not
  7. Carry the rating attached to the opening, not a generic glass description
  8. Lighting quantities change when watts cross zone boundaries
  9. Illustrative example: two watts change two control obligations
  10. Count control functions before assigning device quantities
  11. Release quantities only after the acceptance scope has an owner
  12. Keep the California quantity basis visible in the takeoff workflow

For a GC estimator pricing a new California office at bid-stage CDs, Title 24 changes the relationships behind the quantities, not just the product specifications. An insulation area needs an assembly and layer basis. A glazing area needs a rough-opening basis and orientation. A lighting count needs a wattage schedule and control-zone assignment. Do not carry those three takeoffs independently.

The operative statewide edition is the 2025 Energy Code, Title 24, Part 6, effective for building permit applications submitted on or after January 1, 2026. The California Energy Commission's 2025 overview confirms that application-date basis and the use of 2025 compliance documents.

The practical decision is this: reconcile the energy compliance documents with the architectural and electrical drawings before releasing trade quantities. A complete geometric takeoff is not evidence that the priced assemblies and controls match the compliance design.

Establish the applicable path before measuring the package

This guide concentrates on new nonresidential office construction. It is not a residential checklist, an energy model or a complete code-compliance review. Single-family and multifamily projects have separate provisions. For nonresidential additions and alterations, start with Section 141.0 rather than applying every new-building rule to the existing building. See the 2025 Standards, Table 100.0-A.

Record five inputs on the takeoff cover sheet:

  • Permit application date and assigned Energy Code edition.
  • Occupancy and whether the work is new construction, an addition or an alteration.
  • Climate zone recorded in the compliance package.
  • Prescriptive or performance compliance path.
  • Compliance-document revision matched to the bid drawings and addenda.

These are recommended estimating controls, not a substitute for the designer's code analysis. The broader code-basis review before assigning scope addresses that responsibility.

Under the prescriptive path, Section 140.2 requires the applicable systems and components in Sections 140.3 through 140.10. Under the performance path, Section 140.1 establishes energy budgets; Table 100.0-A retains the applicable mandatory requirements. A performance result does not waive mandatory controls or make the prescriptive envelope table the project's proposed assembly schedule. 2025 Standards, Sections 140.1, 140.2 and Table 100.0-A.

For estimating, price the documented proposed design. If a detail and compliance report disagree, do not quietly choose either the cheapest assembly or the highest insulation value. Request a coordinated answer and record which basis the bid carries.

Read the compliance sheets as a cross-trade register

The CEC's 2025 compliance-document directory distinguishes certificates of compliance (NRCC), installation (NRCI) and acceptance (NRCA). For this review, identify NRCC-ENV-E for the envelope component approach and NRCC-LTI-E for indoor lighting. For performance projects, obtain the proposed-design compliance output and supporting schedules rather than expecting one envelope form to describe the entire model.

The 2025 Nonresidential Compliance Manual, Chapter 2, explains the plan-review interaction under Part 1, Section 10-103: window U-factor and SHGC, insulation R-values, fixture wattages and controls in the compliance documents must be consistent with the construction documents.

Use that interaction to build a pricing register:

Takeoff familyDocuments to reconcileQuantity basis to retainHold point
Opaque envelopeCompliance assembly, wall section and insulation specificationArea by assembly and each specified insulation layerAssembly or layer missing from one document
Vertical fenestrationCompliance schedule, opening schedule and elevationsRough-opening area by product category and orientationArea or performance rating does not reconcile
Indoor lightingNRCC-LTI-E, fixture schedule and control planFixture count, rated watts and assigned control groupsWatts or zone assignments differ
Acceptance workControl design, specifications and certificate requirementsDefined test and documentation scope with an assigned ownerSupply quote excludes programming or testing

The register is deliberately not a compliance scorecard. Its job is to identify the document combination that changes a trade's carry. Retain both disputed values, their source references and the person responsible for resolving them.

For example, a wall detail can show two insulation layers while a trade quote names only cavity insulation. That is not resolved by confirming that the trade measured the correct wall area. The unresolved issue is the assembly behind every square foot.

Insulation quantities belong to assemblies and layers

For prescriptive nonresidential construction, Section 140.3(a)1B addresses roof assembly U-factor and Section 140.3(a)2 addresses exterior wall assembly U-factor. The applicable limits are in Table 140.3-B, C or D; Table 140.3-B is the nonresidential table relevant to the office example. These are overall assembly requirements, not a direction to invert U-factor and purchase that nominal R-value of insulation. 2025 Standards, Section 140.3(a)1B and 2.

The 2025 edition also changed prescriptive roof and wall U-factors, as shown in the CEC overview. Reusing a previous edition's assembly without reconciliation is therefore not an acceptable quantity basis.

The 2025 Nonresidential Compliance Manual, Chapter 3, pages 3-17 through 3-19, explains why framing matters: metal framing conducts heat through the assembly, and continuous insulation is needed in many prescriptive metal-framed wall configurations. It directs assembly evaluation to the applicable reference-appendix data or assembly calculation. The estimator should identify the designed assembly, not redesign it from a batt label.

Illustrative example: one wall area, two priced insulation lines

Assume a synthetic office elevation has:

  • 200 feet of wall length at 12 feet high.
  • Twenty openings, each with a 4-foot by 5-foot rough opening.
  • A coordinated detail specifying cavity insulation and a separate continuous insulation layer over the same net wall field.
  • No additional insulated returns or other openings in this example.

The illustrative quantities are:

  • Gross wall: 200 × 12 = 2,400 square feet.
  • Opening deductions: 20 × 4 × 5 = 400 square feet.
  • Net wall field: 2,400 − 400 = 2,000 square feet.
  • Cavity insulation: 2,000 square feet.
  • Continuous insulation: 2,000 square feet, separately classified and priced.

The field area is not 4,000 square feet. The estimate has two material layers applied to a 2,000-square-foot field. The presence of both layers comes from the illustrative detail, not a universal Title 24 prescription.

The failure is a correct 2,000-square-foot measurement rolled into one generic insulation item. The check is to match the compliance assembly to the section, then map each layer to a quote inclusion. Keep supports, attachment and return treatments separate wherever the actual detail requires them.

Competent estimators may differ about using one assembly item or separate material items. Either can work. What should decide it is whether the item exposes each layer's quantity and ownership when a subcontractor excludes one. For item structure rather than code interpretation, use the insulation takeoff setup guide.

Glazing needs two area bases and an orientation check

Section 100.1 defines fenestration area as rough-opening area. It defines fenestration products to include glazing plus sash, frames, mullions and dividers. Counting visible glass alone is therefore not the Energy Code area basis. 2025 Standards, Section 100.1, fenestration definitions.

Keep a compliance area separate from any glass fabrication or procurement area. They may share a source opening, but they answer different questions. Do not replace the glazing contractor's fabrication dimensions with a rough-opening total.

For prescriptive exterior windows, Section 140.3(a)5A imposes both a total-area limit and a separate west-facing limit. Each uses 40 percent of the applicable gross exterior wall area or six feet times the applicable display perimeter, whichever is greater, subject to the stated exception. Demising walls are excluded from those exterior-wall bases. 2025 Standards, Section 140.3(a)5A.

Illustrative example: the total passes while the west elevation does not

Assume a prescriptive office with no display-perimeter allowance or applicable exception:

  • Gross exterior wall area: 10,000 square feet.
  • Total fenestration rough-opening area: 3,500 square feet.
  • Gross west exterior wall area: 2,000 square feet.
  • West fenestration rough-opening area: 900 square feet.

The illustrative total ratio is 3,500 ÷ 10,000 = 35 percent. The west ratio is 900 ÷ 2,000 = 45 percent. The total passes the area test, but the west elevation exceeds its 800-square-foot limit by 100 square feet.

Now assume the visible-glass takeoff recorded only 760 square feet on the west elevation. That produces 760 ÷ 2,000 = 38 percent, apparently passing because it uses the wrong numerator.

The estimating response is not to delete 100 square feet of glazing. Issue a reconciliation question: is the package actually using the performance path, is the area basis wrong, or must the design change? Hold the shown quantity and document the unresolved basis until directed otherwise.

If the designer replaces that illustrative 100 square feet with the same two-layer opaque assembly used above, glazing falls by 100 square feet while both cavity and continuous insulation rise by 100 square feet. A glazing-only value-engineering credit would miss the replacement wall scope. The glazing takeoff structure guide addresses how to retain product and opening identities.

Carry the rating attached to the opening, not a generic glass description

The 2025 mandatory requirement in Section 120.7(d) is an area-weighted average vertical fenestration assembly U-factor no greater than 0.47, with a stated exception for qualifying WUI/fire-hazard installations. The applicable prescriptive requirements in Section 140.3(a)5B through D also address U-factor, relative SHGC and visible transmittance. Passing the mandatory U-factor check alone does not establish prescriptive compliance. 2025 Standards, Sections 120.7(d) and 140.3(a)5.

For an illustrative mandatory-U-factor screening calculation, assume eligible fixed products with 900 square feet at U-0.40 and 100 square feet at U-0.80. The area-weighted result is:

[(900 × 0.40) + (100 × 0.80)] ÷ 1,000 = 0.44.

That clears the 0.47 screen, but it does not prove the proposed design, SHGC or VT requirements are satisfied. Conversely, substituting the 900-square-foot family to U-0.46 gives 0.494, failing that mandatory screen even though the small family is unchanged.

The decision is to review substitutions by affected area and assembly rating, not by an unweighted average of product types. Require the designer's acceptance of the full compliance effect before treating a proposed substitution as an equivalent buyout.

Lighting quantities change when watts cross zone boundaries

For enclosed spaces, Section 130.1(d)1A through C uses 75 watts as the general-lighting trigger for the applicable skylit, primary sidelit and secondary sidelit daylit zones. Primary and secondary sidelit controls must operate independently where required. Section 130.1(d)2A requires the daylit zones to be shown on the plans. 2025 Standards, Section 130.1(d)1 and 2.

Start from the designed zone boundaries and scheduled luminaire watts. Do not substitute a roomwide fixture count or an arbitrary distance from the facade. For the primary sidelit trigger, include luminaires completely or partially within the zone, as Section 130.1(d)1B specifies.

Illustrative example: two watts change two control obligations

Assume an enclosed office with more than 24 square feet of glazing, no other applicable daylight exception, and these scheduled general-lighting totals:

  • Primary sidelit zone: 74 watts.
  • Secondary sidelit zone: 80 watts.

The primary zone is below its 75-watt trigger. Although the secondary zone reaches 75 watts, Exception 3 to Section 130.1(d) exempts it when primary controls are not required and secondary-zone general lighting is less than 85 watts. Under those illustrative conditions, neither zone requires daylight responsive controls.

An addendum changes the primary-zone total to 76 watts, leaving the secondary zone at 80 watts and leaving fixture counts unchanged. The primary now reaches its trigger. Exception 3 no longer applies to the secondary, which already reaches its own 75-watt trigger. Both zones now require daylight responsive control, independently. 2025 Standards, Section 130.1(d)1B-C and Exception 3.

This is a control-scope reconciliation, not evidence that every two-watt change adds two sensors. The required control functions must be translated through the designed system into equipment, channels, wiring, programming and testing.

Count control functions before assigning device quantities

Section 130.1(d)2B assigns overlapping skylit/sidelit lighting to the skylit zone, and overlapping primary/secondary sidelit lighting to the primary zone. It also addresses control segmentation for luminaires longer than eight feet, including a factory-integral segment exception. Count the physical luminaire once while checking its required control assignments separately. 2025 Standards, Section 130.1(d)2B.

Occupancy zoning is another layer. Section 130.1(c)6D requires general lighting in office spaces greater than 250 square feet to have separately controlled zones no greater than 600 square feet, shown on the plans. An illustrative 1,500-square-foot open office therefore needs at least three occupancy control zones by area, not necessarily three sensors. 2025 Standards, Section 130.1(c)6D.

The judgment call is whether a quote's integrated controls package covers all these functions. Do not demand a separate device for every function if one designed system performs several. Instead, ask the electrical bidder to identify the controlled luminaire groups, equipment basis and included programming. The electrical takeoff setup guide covers item organization without turning code functions into invented hardware ratios.

Release quantities only after the acceptance scope has an owner

For the office scope discussed here, Section 130.4(a) requires applicable controls to meet acceptance requirements before occupancy. It specifically identifies daylight controls, shutoff controls and demand responsive lighting controls in subsections 3 through 5. The CEC forms directory lists NRCA-LTI-02-A, -03-A and -04-A for those respective control families. 2025 Standards, Section 130.4(a).

Site-built fenestration also has acceptance and matching-label-certificate requirements under Section 110.6(a)6. Do not apply that requirement indiscriminately to every factory-manufactured window. 2025 Standards, Section 110.6(a)6.

Before carrying the trade number, resolve:

  1. Which assembly or control group does each quantity represent?
  2. Does its specification match the current compliance design?
  3. Who supplies, installs, programs and tests the required system?
  4. Does a stated exclusion have another assigned owner?
  5. Which open question could change more than one trade's quantity?

This is the recommended release check. It does not certify the building. General measurement errors belong in the construction takeoff mistakes guide; the California-specific task is preserving the dependency between compliance basis and priced work.

Keep the California quantity basis visible in the takeoff workflow

The useful system is one where the measured opening, insulation layer and controlled lighting group retain their sources while the team reconciles scope. The general AI takeoff process supplies the broader workflow; this article adds the California compliance hold points.

Piper's takeoff workflow supports manual, assisted and agentic takeoff from PDF drawings in one editable file. Assisted tools propose boundaries, traces or similar-symbol candidates for inspection and correction. Agentic takeoff starts with a defined measurement task and produces editable measurements grouped into items for review.

For this package, review sheet scale, revision, opening deductions, insulation item assignments and lighting coverage before using the quantities. Takeoff stays alongside drawings, specifications, trade scopes and bid review, but the team still owns the compliance interpretation, pricing basis and carry decision. A measurable area is not a code approval.

FAQ

Which California Energy Code edition should a 2026 takeoff use?

The 2025 Energy Code applies to building permit applications submitted on or after January 1, 2026, according to the CEC's 2025 overview. Confirm the actual permit application basis before converting a legacy design to current-edition assemblies or controls; the bid date alone is not the edition selector.

Should I measure visible glass or rough openings for Title 24?

Use rough-opening area for the Energy Code fenestration area basis under Section 100.1. Keep that area separate from glass fabrication quantities. Retain opening identities and orientation so total and west-facing prescriptive area checks under Section 140.3(a)5A can be reconciled without remeasuring unrelated work.

Does the 75-watt daylight trigger mean one sensor per zone?

No. Section 130.1(d) establishes control obligations, not a universal sensor-to-zone purchasing ratio. Check the applicable exceptions and independent control assignments, then obtain the designed system's equipment and programming basis. The illustrative 74-to-76-watt change above affects both primary and secondary control obligations without changing fixture counts.

Can a performance compliance result eliminate mandatory lighting controls?

No. Table 100.0-A retains applicable mandatory requirements for the performance path, including Section 130.1 controls. Price the documented proposed design and its control system. If the lighting plan and compliance output disagree, obtain a coordinated clarification rather than treating a passing energy budget as a control-scope exclusion.